'''American wire gauge''' ('''AWG''') tells the diameter of an electrical conductor.  A conductor's current capacity depends upon the resistance per unit length and the temperature rating of the insulation.  Wire type THHN is rated at 90 °C, and it has an added nylon jacket.
'''American wire gauge''' ('''AWG''') tells the diameter of an electrical conductor.  The conductor's current capacity depends upon the resistance per unit length and the temperature rating of the insulation.  Wire type THHN is rated at 90 °C, and it has an added nylon jacket.


Electric welders use a lot of current for short periods.  The National Electrical Code (NEC) provides for welders by allowing wire size of only half the capacity that would otherwise be required.  For example, a 50 amp circuit breaker, a 50 amp outlet, but only 10 AWG wire.
Electric welders use a lot of current for short periods.  The National Electrical Code (NEC) provides for welders by allowing wire size of only half the capacity that would otherwise be required.  For example, a 50 amp circuit breaker, a 50 amp outlet, but only 10 AWG wire.
Line 5: Line 5:
A similar exception is made for protective ground wires, which can have only half the capacity of the current carrying conductors.
A similar exception is made for protective ground wires, which can have only half the capacity of the current carrying conductors.


==Tables of AWG wire sizes==
==Tables of AWG wire sizes simplified from [https://en.wikipedia.org/wiki/American_wire_gauge#Tables_of_AWG_wire_sizes Wikipedia]==
Most of the following table came from [https://en.wikipedia.org/wiki/American_wire_gauge#Tables_of_AWG_wire_sizes Wikipedia].
Parts of the following following table apply only to solid wire.  The diameter of stranded wire is larger than indicated.
Diameter and turns apply only to solid wire.  The total diameter of stranded wire is larger than solid, even though the conductive cross sections are the same.


{| class="wikitable" style="textalign:center;"
{| class="wikitable" style="textalign:center;"
! rowspan=4 | AWG
! rowspan=4 | AWG
! rowspan=3 colspan=2 | Diameter <br/> (of solid wire)
! rowspan=3 colspan=2 | Diameter <br/> (of solid wire)
! rowspan=3 colspan=2 | Turns of wire, <br />without insulation <br/> (with solid wire)
! rowspan=3 colspan=2 | Turns of wire, <br />without insulation <br/> (of solid wire)
! rowspan=3 colspan=2 | Area
! rowspan=3 colspan=2 | Area
! colspan=8 | Copper wire
! colspan=8 | Copper wire
Line 126: Line 125:
|}
|}


==Number of wires in conduit==
==Number of conductors in tube==
National Electrical Code Article 348-6 limits the total cross sectional area of wires to a certain percentage of the  cross sectional area of a conduit.
The electrical code limits the total cross sectional area of conductors to a certain percentage or the  cross sectional area of a conduit.


{| class="wikitable" style="textalign:center;"
{| class="wikitable" style="textalign:center;"
|+Allowable fill
!Conductors
!Conductors
!Percent filled
!Percent filled
Line 141: Line 139:
|}
|}


 
For type THHN wire, this works out to:
For type THHN wire installed in standard EMT conduits, allowable fill works out to:


{| class="wikitable" style="textalign:center;"
{| class="wikitable" style="textalign:center;"
|+Maximum THHN conductors in a conduit
!AWG !! 1/2 !! 3/4 !! 1 !! 1 1/4 !! 1 1/2
!AWG !! {{frac|1|2}}
! {{frac|3|4}}
! 1  
! {{frac|1|1|4}}
! {{frac|1|1|2}}
|-
|-
! 14  
! 14  
Line 172: Line 164:


==Number of conductors in a box==
==Number of conductors in a box==
Article 370-6 limits the number of conductors entering a box.  A conductor that passes through a box, without any connection, counts as one conductor. A conductor that begins and ends within a box is not counted at all.  The size of devices, such as outlets and switches, must be subtracted from the capacity of the box.
Article 370-6 limits the number of conductors entering a box.  A conductor that passes through a box, without any connection, counts as one conductor.
 
{| class="wikitable" style="textalign:center;"
|+ Capacity of selected box sizes
!Box type !! Cubic inches !! 14 !! 12 !! 10 !! 8 !! 6
|-
! 4 x {{frac|1|1|4}}  Round !! 12.5
| 6 || 5 || 5 || 4 || 0
|-
! 4 x {{frac|1|1|4}}  Square !! 18.0
| 9 || 8 || 7 || 6 || 0
|-
! 4 x {{frac|1|1|2}}  Square !! | 21.0
| 10 || 9 || 8 || 7 || 0
|-
! 4 x {{frac|2|1|8}} Square !! 30.3
| 15 || 13 || 12 || 10 || 6
|-
! {{frac|4|11|16}} x {{frac|2|1|8}} Square !! 42.0
| 21 || 18 || 16 || 14 || 6
Please note that all contributions to Noisebridge are considered to be released under the Creative Commons Attribution-NonCommercial-ShareAlike (see Noisebridge:Copyrights for details). If you do not want your writing to be edited mercilessly and redistributed at will, then do not submit it here.
You are also promising us that you wrote this yourself, or copied it from a public domain or similar free resource. Do not submit copyrighted work without permission!

To protect the wiki against automated edit spam, we kindly ask you to solve the following CAPTCHA:

Cancel Editing help (opens in new window)

Templates used on this page: