American wire gauge: Difference between revisions
(caption) |
(tweek) |
||
Line 126: | Line 126: | ||
|} | |} | ||
==Number of | ==Number of wires in conduit== | ||
National Electrical Code Article 348-6 limits the total cross sectional area of | National Electrical Code Article 348-6 limits the total cross sectional area of wires to a certain percentage of the cross sectional area of a conduit. | ||
{| class="wikitable" style="textalign:center;" | {| class="wikitable" style="textalign:center;" | ||
Line 142: | Line 142: | ||
For type THHN wire, this works out to: | For type THHN wire in standard EMT conduits, this works out to: | ||
{| class="wikitable" style="textalign:center;" | {| class="wikitable" style="textalign:center;" |
Revision as of 19:57, 21 February 2017
American wire gauge (AWG) tells the diameter of an electrical conductor. A conductor's current capacity depends upon the resistance per unit length and the temperature rating of the insulation. Wire type THHN is rated at 90 °C, and it has an added nylon jacket.
Electric welders use a lot of current for short periods. The National Electrical Code (NEC) provides for welders by allowing wire size of only half the capacity that would otherwise be required. For example, a 50 amp circuit breaker, a 50 amp outlet, but only 10 AWG wire.
A similar exception is made for protective ground wires, which can have only half the capacity of the current carrying conductors.
Tables of AWG wire sizes
Most of the following table came from Wikipedia. Diameter and turns apply only to solid wire. The total diameter of stranded wire is larger than solid, even though the conductive cross sections are the same.
AWG | Diameter (of solid wire) |
Turns of wire, without insulation (of solid wire) |
Area | Copper wire | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Resistance/length | Ampacity | |||||||||||||
60 °C | 75 °C | 90 °C | ||||||||||||
(in) | (mm) | (per in) | (per cm) | (kcmil) | (mm2) | (mΩ/m | (mΩ/ft | (A) | ||||||
0000 (4/0) | 0.4600 | 11.684 | 2.17 | 0.856 | 212 | 107 | 0.1608 | 0.04901 | 195 | 230 | 260 | |||
000 (3/0) | 0.4096 | 10.405 | 2.44 | 0.961 | 168 | 85.0 | 0.2028 | 0.06180 | 165 | 200 | 225 | |||
00 (2/0) | 0.3648 | 9.266 | 2.74 | 1.08 | 133 | 67.4 | 0.2557 | 0.07793 | 145 | 175 | 195 | |||
0 (1/0) | 0.3249 | 8.251 | 3.08 | 1.21 | 106 | 53.5 | 0.3224 | 0.09827 | 125 | 150 | 170 | |||
1 | 0.2893 | 7.348 | 3.46 | 1.36 | 83.7 | 42.4 | 0.4066 | 0.1239 | 110 | 130 | 145 | |||
2 | 0.2576 | 6.544 | 3.88 | 1.53 | 66.4 | 33.6 | 0.5127 | 0.1563 | 95 | 115 | 130 | |||
3 | 0.2294 | 5.827 | 4.36 | 1.72 | 52.6 | 26.7 | 0.6465 | 0.1970 | 85 | 100 | 115 | |||
4 | 0.2043 | 5.189 | 4.89 | 1.93 | 41.7 | 21.2 | 0.8152 | 0.2485 | 70 | 85 | 95 | |||
5 | 0.1819 | 4.621 | 5.50 | 2.16 | 33.1 | 16.8 | 1.028 | 0.3133 | ||||||
6 | 0.1620 | 4.115 | 6.17 | 2.43 | 26.3 | 13.3 | 1.296 | 0.3951 | 55 | 65 | 75 | |||
7 | 0.1443 | 3.665 | 6.93 | 2.73 | 20.8 | 10.5 | 1.634 | 0.4982 | ||||||
8 | 0.1285 | 3.264 | 7.78 | 3.06 | 16.5 | 8.37 | 2.061 | 0.6282 | 40 | 50 | 55 | |||
9 | 0.1144 | 2.906 | 8.74 | 3.44 | 13.1 | 6.63 | 2.599 | 0.7921 | ||||||
10 | 0.1019 | 2.588 | 9.81 | 3.86 | 10.4 | 5.26 | 3.277 | 0.9989 | 30 | 35 | 40 | |||
11 | 0.0907 | 2.305 | 11.0 | 4.34 | 8.23 | 4.17 | 4.132 | 1.260 | ||||||
12 | 0.0808 | 2.053 | 12.4 | 4.87 | 6.53 | 3.31 | 5.211 | 1.588 | 20 | 25 | 30 | |||
13 | 0.0720 | 1.828 | 13.9 | 5.47 | 5.18 | 2.62 | 6.571 | 2.003 | ||||||
14 | 0.0641 | 1.628 | 15.6 | 6.14 | 4.11 | 2.08 | 8.286 | 2.525 | 15 | 20 | 25 | |||
15 | 0.0571 | 1.450 | 17.5 | 6.90 | 3.26 | 1.65 | 10.45 | 3.184 | ||||||
16 | 0.0508 | 1.291 | 19.7 | 7.75 | 2.58 | 1.31 | 13.17 | 4.016 | 22*free air | 13*enclosed | 18 | |||
17 | 0.0453 | 1.150 | 22.1 | 8.70 | 2.05 | 1.04 | 16.61 | 5.064 | ||||||
18 | 0.0403 | 1.024 | 24.8 | 9.77 | 1.62 | 0.823 | 20.95 | 6.385 | 10 | 14 | 16 | |||
19 | 0.0359 | 0.912 | 27.9 | 11.0 | 1.29 | 0.653 | 26.42 | 8.051 | — | — | — | |||
20 | 0.0320 | 0.812 | 31.3 | 12.3 | 1.02 | 0.518 | 33.31 | 10.15 | 7.5 | 11 | — | |||
21 | 0.0285 | 0.723 | 35.1 | 13.8 | 0.810 | 0.410 | 42.00 | 12.80 | — | — | — | |||
22 | 0.0253 | 0.644 | 39.5 | 15.5 | 0.642 | 0.326 | 52.96 | 16.14 | 7 | 5 | — | |||
23 | 0.0226 | 0.573 | 44.3 | 17.4 | 0.509 | 0.258 | 66.79 | 20.36 | — | — | — | |||
24 | 0.0201 | 0.511 | 49.7 | 19.6 | 0.404 | 0.205 | 84.22 | 25.67 | 3.5 | 2.1 | — | |||
25 | 0.0179 | 0.455 | 55.9 | 22.0 | 0.320 | 0.162 | 106.2 | 32.37 | — | — | — | |||
26 | 0.0159 | 0.405 | 62.7 | 24.7 | 0.254 | 0.129 | 133.9 | 40.81 | 2.2 | 1.3 | — | |||
27 | 0.0142 | 0.361 | 70.4 | 27.7 | 0.202 | 0.102 | 168.9 | 51.47 | — | — | — | |||
28 | 0.0126 | 0.321 | 79.1 | 31.1 | 0.160 | 0.0810 | 212.9 | 64.90 | 1.4 | 0.85 | — | |||
29 | 0.0113 | 0.286 | 88.8 | 35.0 | 0.127 | 0.0642 | 268.5 | 81.84 | — | — | — | |||
30 | 0.0100 | 0.255 | 99.7 | 39.3 | 0.101 | 0.0509 | 338.6 | 103.2 | 0.86 | 0.52 | — | |||
31 | 0.00893 | 0.227 | 112 | 44.1 | 0.0797 | 0.0404 | 426.9 | 130.1 | — | — | — | |||
32 | 0.00795 | 0.202 | 126 | 49.5 | 0.0632 | 0.0320 | 538.3 | 164.1 | 0.53 | 0.3 | — | |||
33 | 0.00708 | 0.180 | 141 | 55.6 | 0.0501 | 0.0254 | 678.8 | 206.9 | — | — | — | |||
34 | 0.00630 | 0.160 | 159 | 62.4 | 0.0398 | 0.0201 | 856.0 | 260.9 | 0.3 | 0.180 | — | |||
35 | 0.00561 | 0.143 | 178 | 70.1 | 0.0315 | 0.0160 | 1079 | 329.0 | — | — | — | |||
36 | 0.00500 | 0.127 | 200 | 78.7 | 0.0250 | 0.0127 | 1361 | 414.8 | — | — | — | |||
37 | 0.00445 | 0.113 | 225 | 88.4 | 0.0198 | 0.0100 | 1716 | 523.1 | — | — | — | |||
38 | 0.00397 | 0.101 | 252 | 99.3 | 0.0157 | 0.00797 | 2164 | 659.6 | — | — | — | |||
39 | 0.00353 | 0.0897 | 283 | 111 | 0.0125 | 0.00632 | 2729 | 831.8 | — | — | — | |||
40 | 0.00314 | 0.0799 | 318 | 125 | 0.00989 | 0.00501 | 3441 | 1049 | — | — | — |
Number of wires in conduit
National Electrical Code Article 348-6 limits the total cross sectional area of wires to a certain percentage of the cross sectional area of a conduit.
Conductors | Percent filled |
---|---|
1 | 53 |
2 | 31 |
3 or more | 40 |
For type THHN wire in standard EMT conduits, this works out to:
AWG | 1⁄2 | 3⁄4 | 1 | 1 1⁄4 | 1 1⁄2 |
---|---|---|---|---|---|
14 | 13 | 24 | 39 | 69 | 94 |
12 | 10 | 18 | 29 | 51 | 70 |
10 | 6 | 11 | 18 | 32 | 44 |
8 | 3 | 5 | 9 | 16 | 22 |
6 | 1 | 4 | 6 | 11 | 15 |
4 | 1 | 2 | 4 | 7 | 9 |
Number of conductors in a box
Article 370-6 limits the number of conductors entering a box. A conductor that passes through a box, without any connection, counts as one conductor. A conductor that begins and ends within a box is not counted at all. The size of devices, such as outlets and switches, must be subtracted from the capacity of the box.
Box type | Cubic inches | 14 | 12 | 10 | 8 | 6 |
---|---|---|---|---|---|---|
4 x 1 1⁄4 Round | 12.5 | 6 | 5 | 5 | 4 | 0 |
4 x 1 1⁄4 Square | 18.0 | 9 | 8 | 7 | 6 | 0 |
4 x 1 1⁄2 Square | 21.0 | 10 | 9 | 8 | 7 | 0 |
4 x 2 1⁄8 Square | 30.3 | 15 | 13 | 12 | 10 | 6 |
4 11⁄16 x 2 1⁄8 Square | 42.0 | 21 | 18 | 16 | 14 | 6 |